Application;

At power distribution stations, house hold premises at industrial plants in cable ducts and pipes. Where there is no risk of mechanical damage.

Construction;

1. Solid or stranded copper conductor
2. PVC insulation
3. Polyester tape
4. PVC outer sheath

Construction;

Technical Data

Rated Cross Section

Overall Diameter of Cable

(Approx)

Current Carrying Capacity

Conductor DC Resistance

Short Circuit Current

Net Weight (Approx)

Delivery Length (Approx)

 

mm²

 

mm

 

ohm/km (20°C)

 

ohm/km (70°C)

 

kA (1 sn)

 

kg/km

 

mt

Air

Ground

3 x 25

20,30

106

133

0,727

0,870

2,88

910

1000

3 x 35

23,50

129

159

0,524

0,627

4,03

1.230

1000

3 x 50

26,90

157

188

0,387

0,463

5,75

1.640

1000

3 x 70

29,10

199

232

0,268

0,321

8,05

2.240

1000

3 x 95

34,90

246

280

0,193

0,231

10,93

3.110

1000

3 x 120

37,90

285

318

0,153

0,183

13,80

3.840

1000

3 x 150

40,50

326

359

0,124

0,148

17,25

4.700

1000

3 x 185

44,70

374

406

0,0991

0,119

21,28

5.830

1000

3 x 240

50,90

445

473

0,0754

0,090

27,60

7.580

1000

3 x 300

55,10

511

535

0,0601

0,072

34,50

9.420

1000

3 x 400

62,30

597

613

0,0470

0,056

41,20

12.180

500

4 x 25

21,30

106

133

0,727

0,870

2,88

1.180

1000

4 x 35

24,70

129

159

0,524

0,627

4,03

1.580

1000

4 x 50

27,70

157

188

0,387

0,463

5,75

2.110

1000

4 x 70

30,70

199

232

0,268

0,321

8,05

2.890

1000

4 x 95

36,30

246

280

0,193

0,231

10,93

4.010

1000

4 x 120

39,30

285

318

0,153

0,183

13,80

4.970

1000

4 x 150

43,10

326

359

0,124

0,148

17,25

6.130

1000

4 x 185

47,50

374

406

0,0991

0,119

21,28

7.640

1000

4 x 240

53,30

445

473

0,0754

0,090

27,60

9.960

1000

4 x 300

58,30

511

535

0,0601

0,072

34,50

12.380

500

4 x 400

62,30

597

613

0,0470

0,056

41,20

15.950

500